5 Installation at Site
25 of 104
mini-Compacta
2317.886/16-EN
5 Installation at Site
5.1 Safety regulations
DANGER
Improper installation in potentially explosive atmospheres
Explosion hazard!
Damage to the lifting unit!
▷
Comply with the applicable local explosion protection regulations.
▷
Observe the information in the technical product literature and on the name
plates of tank and motor.
WARNING
Hot motor surface
Risk of injury!
▷
Allow the motor to cool down to ambient temperature.
CAUTION
Incorrect connection of the three-phase motor
Damage to the lifting unit!
▷
Always use a 3-pole mechanically interlocked K-type automatic circuit breaker
for external protection.
CAUTION
Incorrect installation of connections and signalling devices
A failure of the lifting unit can cause damage to property by flooding due to the
risk of backflow from the sewage system.
▷
Fit operator-supplied mains-independent alarm equipment (e.g. alarm
switchgear).
▷
Take suitable measures at the site to prevent overflow/flooding (e.g. a swing
check valve in the floor drain, or similar).
NOTE
If uninterrupted waste water drainage is required, e.g. in basement flats,
restaurants/pubs, cinemas, etc., lifting units must be fitted with a stand-by pump
(dual-pump unit UZ) in accordance with EN 12 050-1.
5.2 Checks to be carried out prior to installation
WARNING
Installation on mounting surfaces which are unsecured and cannot support the
load
Personal injury and damage to property!
▷
Use a concrete of compressive strength class C12/15 which meets the
requirements of exposure class X0 to EN 206-1.
▷
The mounting surface must have set and must be completely horizontal and
even.
▷
Observe the weights indicated.