10 Related Documents
60 of 80
KSB Delta Primo
1983.811/02-EN
Parameter
Description
Factory setting
Possible
settings
Min.
value
Max.
value
Read access
right
Write access
right
3-4-3-15
F nominal of VFD
Nominal frequency of
frequency inverters
50
50.. 50
50
50
Everybody
Service
3-4-3-16
I nominal of VFD
Nominal amperage of
frequency inverters
4
0.. 450
0
450
Everybody
Service
3-4-3-17
RPM nominal of VFD
Nominal speed of frequency
inverters
2880
0.. 10000
0
10000
Everybody
Service
3-4-3-20
Motor Speed Unit
Motor speed unit
rpm
rpm,
Hz
-
-
Everybody
Service
3-4-3-21
Digital I/P 33 func.
Selecting the digital input
No function
No function,
coasting stop
inv.
-
-
Everybody
Service
3-4-3-22
Digital I/P 29 func.
Selecting the digital input
No function
No function,
jog function,
jog function
-
-
Everybody
Service
3-4-3-23
Jog frequency
Speed in manual mode
50
30.. 50
30
50
Everybody
Service
3-4-3-24
Jog ramp time
Ramp time
5
0,04.. 3600
0,04
3600
Everybody
Service
3-4-3-25
Coasting select
Selecting the manual mode
Digital and bus
Digital input,
bus,
digital and bus,
digital or bus
-
-
Everybody
Service
3-4-3-26
Start select
Selecting the start signal
Digital and bus
Digital input,
bus,
digital and bus,
digital or bus
-
-
Everybody
Service
3-4-3-27
Slip Compensation
Slip compensation
0
-400.. 399
-400
399
Everybody
Service
3-4-3-5
No flow detection
Accuracy with which a
minimum flow is detected
(procedure for stopping the
pumps)
-
-
-
-
Everybody
Service
3-4-3-5-1
No flow bandwith
Bandwidth of flow detection
6
0.. 50
0
50
Service
Service
3-4-3-5-2
No flow time
Flow detection time in
seconds
16
0.. 60
0
600
Service
Service
3-4-3-5-3
No flow step
Step height of flow detection
in percent
1
1.. 50
1
50
Service
Service
3-4-3-5-4
No flow max. power
Flow detection is active
below this pump load in
percent
100
0.. 100
0
100
Service
Service
3-4-4
WSD settings
Configuring water flow
detection
-
-
-
-
Everybody
Nobody
3-4-4-1
Nbr of refreshments
Number of water
replacement cycles
30
0.. 99
0
99
Everybody
Service
3-4-4-2
Refresh time span
Duration of water
replacement procedure in
hours
24
0.. 999
0
999
Everybody
Service
3-4-4-3
Average room temp.
Measured average ambient
temperature
25
0.. 50
0
50
Everybody
Service