10 Related Documents
58 of 80
KSB Delta Primo
1983.811/02-EN
Parameter
Description
Factory setting
Possible
settings
Min.
value
Max.
value
Read access
right
Write access
right
3-4-1-4-9-2
Level 1 closed
Level for closing gate valve
to stop filling inlet tank
90
0.. 99
0
99
Everybody
Service
3-4-1-4-9-3
Level 1A open
Second level (timer-based)
for opening gate valve to
start filling
40
0.. 99
0
99
Everybody
Service
3-4-1-4-9-4
Level 1A closed
Second level (timer-based)
for closing gate valve to stop
filling
60
0.. 99
0
99
Everybody
Service
3-4-1-4-10
Supply valve prop.
Use of a proportional valve
to fill inlet tank
-
-
-
-
Everybody
Nobody
3-4-1-4-10-1
Level setpoint 1
Level in inlet tank at which
valve is completely closed
80
0.. 99
0
99
Everybody
Service
3-4-1-4-10-2
Level setpoint 1A
Second level (timer-based)
in inlet tank at which valve is
completely closed
40
0.. 99
0
99
Everybody
Service
3-4-1-4-10-3
Hysteresis
Setting the hysteresis for
fully open valve
15
0.. 99
0
99
Everybody
Service
3-4-1-4-10-4
Sample time
Measurement cycle for
measuring to control
proportional valve
10
0.. 99
0
99
Everybody
Service
3-4-1-4-10-5
Analog output
Configuring the analog
output
4-20mA
4 - 20 mA,
0 - 20 mA
-
-
Everybody
Service
3-4-1-5
Auto. Setpoint Redu.
Automatic setpoint reduction
in case of inlet pressure
drop
-
-
-
-
Everybody
Nobody
3-4-1-5-1
ASR function
Automatic setpoint reduction
in case of inlet pressure
drop
Off
Off,
on
-
-
Everybody
Service
3-4-1-5-2
Switch on point
Re-start point
200
100.. 400
100
400
Everybody
Service
3-4-1-5-3
Inlet Set point
Entering the minimum inlet
pressure setpoint
100
0.. 400
0
400
Everybody
Service
3-4-1-5-4
Switch off point
Stop point
90
0.. 100
0
100
Everybody
Service
3-4-1-5-5
Proportional const.
Proportional constant of PID
controller
3
0.. 10
0
10
Everybody
Service
3-4-1-5-6
Integral time
Integral constant of PID
controller
1
0.. 60
0
60
Everybody
Service
3-4-1-5-7
Differential time
Differential constant of PID
controller
0
0.. 99
0
99
Everybody
Service
3-4-1-5-9
Switch On time
Time to pump start
5
0.. 60
0
60
Service
Service
3-4-1-5-10
Switch Off time
Time to pump stop
5
0.. 60
0
60
Service
Service
3-4-2
Discharge
Discharge-side
parameterisation
-
-
-
-
Everybody
Service