10 Related Documents
61 of 80
KSB Delta Primo
1983.811/02-EN
Parameter
Description
Factory setting
Possible
settings
Min.
value
Max.
value
Read access
right
Write access
right
3-4-4-4
Room temp. time span
Duration of ambient
temperature measurement
in hours
24
0.. 999
0
999
Everybody
Service
3-4-5
MPO settings
Configuring the multiple
pump operation functions
-
-
-
-
Everybody
Customer
3-4-5-1
High Load Profile
Characteristic of pump
Cubic
Linear,
cubic
-
-
Customer
Develop
3-4-5-2
Rated Freq
Rated frequency of pump
50
45.. 50
45
50
Everybody
Service
3-4-5-3
Switch On Freq.
Start frequency of pump
49
31.. 50
31
50
Everybody
Service
3-4-5-4
Switch Off Freq.
Stop frequency of pump
31
30.. 49
30
49
Everybody
Service
3-4-5-5
Cubic setting
Cubic setting
-
-
-
-
Everybody
Service
3-4-5-5-1
Power 1
Power 1 of pump
2
0.. 100
0
100
Everybody
Service
3-4-5-5-2
Power 2
Power 2 of pump
2
0.. 100
0
100
Everybody
Service
3-4-5-6
Linear setting
Linear setting of pump
-
-
-
-
Everybody
Service
3-4-5-6-1
Power 1
Power 1 of pump
2
0.. 100
0
100
Everybody
Service
3-4-5-6-2
Power 2
Power 2 of pump
2
0.. 100
0
100
Everybody
Service
3-4-5-6-3
Power 3
Power 3 of pump
2
0.. 100
0
100
Everybody
Service
3-4-5-6-4
Power 4
Power 4 of pump
2
0.. 100
0
100
Everybody
Service
3-4-5-7
Motor settings
Motor settings
-
-
-
-
Everybody
Nobody
3-4-5-7-1
Rated Motor Power
Rated power of motor as per
name plate
2
0.. 110
0
110
Everybody
Service
3-4-5-7-2
Rated Motor Speed
Rated speed of motor as per
name plate
1450
300.. 3600
300
3600
Everybody
Service
3-4-5-7-3
Rated Freq
Rated frequency of motor as
per name plate
50
45.. 50
45
50
Everybody
Service
3-4-5-7-4
Rated Current
Rated current of motor as
per name plate
10
0,1.. 999
0,1
999
Everybody
Service
3-4-5-7-5
Rated Cosphi
Rated cos phi of motor as
per name plate
1
0,1.. 0,99
0,1
0,99
Everybody
Service
3-4-5-8
Pump parameters
Pump settings
-
-
-
-
Everybody
Nobody
3-4-5-8-1
Rated Pump Speed
Rated speed of pump for
rated H/Q characteristic
curve
2900
300.. 3600
300
3600
Everybody
Service
3-5
Pressure
Configuring the system
pressure
-
-
-
-
Everybody
Nobody
3-5-1
Set point
Entering the pressure
setpoint (system pressure)
400
0.. 1000
0
1000
Everybody
Customer