10 Related Documents
53 of 80
KSB Delta Primo
1983.811/02-EN
Parameter
Description
Factory setting
Possible
settings
Min.
value
Max.
value
Read access
right
Write access
right
1-1-3
RDP switch
Detection of dry running
protection via pressure
switch is activated/
deactivated.
-
Not available,
available
-
-
Everybody
Nobody
1-1-4
Inlet pressure
Displaying the suction-side
pressure
-
-
-
-
Everybody
Nobody
1-1-5
Level content in %
Displaying the water level in
inlet tank in percent
-
-
-
-
Everybody
Nobody
1-1-6
Level height
Displaying the water level in
the inlet tank
-
-
-
-
Everybody
Nobody
1-1-7
Ambient temp. (WSD)
Displaying the measured
ambient temperature if water
flow detection is available
-
-
-
-
Everybody
Nobody
1-1-8
Digital inputs
Displaying the status of the
digital inputs
-
-
-
-
Service
Service
1-1-9.2
Position suppl.valve
Position of supply valve
Open
Open,
closed
-
-
Everybody
Nobody
1-1-9.1
Position suppl.valve
Position of proportional
supply valve 0 % ... 100 %
0
0...100
0
100
Everybody
Nobody
1-1-10
Power down speed
Calculated stop speed if
zero-flow detection is
activated in energy-saving
mode
-
-
-
-
Service
Nobody
1-1-14
WSD pulses tank 1
Water flow detection,
number of fills in tank 1
0
-
-
-
Everybody
Nobody
1-1-15
WSD pulses tank 2
Water flow detection,
number of fills in tank 2
0
-
-
-
Everybody
Nobody
1-1-16
WSD pulses tank 3
Water flow detection,
number of fills in tank 3
0
-
-
-
Everybody
Nobody
1-2
Pumps
Pump-relevant status
information
-
-
-
-
Everybody
Nobody
1-2-1
Operating mode
Setting the operating mode
for each individual pump
-
-
-
-
Everybody
Everybody
1-2-1.1.1
Pump number
Entering the pump number
for which the operating
mode is configured
1
1.. 3
1
3
Everybody
Everybody
1-2-1.2.1
Operating mode
Displaying the operating
status of the pump
1
Automatic,
manual On
(10 s),
manual Off
-
-
Everybody
Everybody
1-2-2
Pump load
Displaying the pump load
-
-
-
-
Everybody
Nobody
1-2-3
Thermal fail. flags
Bit-based display of status of
all thermal fault inputs
-
Not tripped
Tripped
-
-
Service
Nobody
1-2-4
Running hours pump
Displaying the operating
hours per pump
-
-
-
-
Everybody
Nobody