10 Related Documents
63 of 80
KSB Delta Primo
1983.811/02-EN
Parameter
Description
Factory setting
Possible
settings
Min.
value
Max.
value
Read access
right
Write access
right
3-6-4
Max. run time
After the time has lapsed,
the system switches over to
the next pump.
86400
0.. 604800
0
604800 Everybody
Service
3-6-5
Start delay
Start delay of pumps if
pressure remains below
setpoint
t
1
0.. 999
0
999
Everybody
Service
3-6-6
Stop delay
Stop delay of pumps if
pressure remains at setpoint
1
0.. 999
0
999
Everybody
Service
3-6-8
RDP delay
Stop delay following
detection of dry running
occurrence
10
0.. 999
0
999
Everybody
Service
3-6-9
High/low alarm delay
Time window for
suppressing alerts when
system pressure is
exceeded/undershot
60
10.. 999
10
999
Everybody
Service
3-6-10
WSD 1 pulse length
Water flow detection 1,
length of pulse in seconds
4
0.. 99
0
99
Everybody
Service
3-6-11
WSD 2 pulse length
Water flow detection 2,
length of pulse in seconds
4
0.. 99
0
99
Everybody
Service
3-6-12
WSD 3 pulse length
Water flow detection 3,
length of pulse in seconds
4
0.. 99
0
99
Everybody
Service
3-6-13
Sys. start up delay
Start delay following re-start
10
0.. 32
0
32
Service
Service
3-7
Time/Date
Date and time
-
-
-
-
Everybody
Nobody
3-7-1
Date
Setting the date
-
-
-
-
Everybody
Customer
3-7-1.1.1
Year
Setting the year
...
1970.. 2099
1970
2099
Everybody
Customer
3-7-1.1.2
Month
Setting the month
1
1.. 12
1
12
Everybody
Customer
3-7-1.1.3
Day
Setting the day
1
1.. 31
1
31
Everybody
Customer
3-7-2
Time
Setting the time
-
-
-
-
Everybody
Customer
3-7-2.1.1
Time
Setting the time in the format
HH:MM:SS
0
0.. 86399
0
86399
Everybody
Customer
3-7-3
Check run mode
Basic setting for forced start
(check run)
Interval
Off,
digital input,
interval,
day-based,
week-based
-
-
Everybody
Customer
3-7-4
Check run interval
Interval-controlled forced
start (check run);
the pumps are started at
fixed, defined intervals.
86400
0.. 1000000
0
1000000 Everybody
Service
3-7-5
Check run at
Day-controlled forced start
(check run);
the pumps are started at a
defined time
-
-
-
-
Everybody
Customer
3-7-5.1.1
Hours
Hours for daily forced start
(check run)
0
0.. 23
0
23