8
AMTRONIC R1300
II – 2 ACTAIR NG 240 to 700 and DYNACTAIR NG 120 to 350
Adaptation kit for
Actair NG and
Dynactair NG
A- Position the adaptations elements for Actair NG and Dynactair NG
B- Fix the adapter kit plate to the actuator interface with 4 M5 screws
C- Separate the unit (item 9) from the base (item 4) by unscrewing the 6 screws (item 10) (TORX T20
screwdriver).
D- Remove distribution plate A or B (item 7) with its two seals (item 5).
E- Fix the base (item 4) to the actuator using 4 M5 seals + washers (item 5) (TORX T20 screwdriver).
Tightening torque = 2.5 Nm
Check the correct position of the seal (item 3).
F- Reposition distribution plate A or B (item 7) with its two seals (item 8).
Check the correct position of the seal (item 8).
G- Position the unit (item 9) on the base (item 4) taking care to engage the column (item 11) with the adapter and tighten the 6
M4 screws (item 10) (TORX T20 screwdriver).
Check the correct position of the seal (item 6).