![KSB AMTRONIC R1300 User Instructions Download Page 26](http://html1.mh-extra.com/html/ksb/amtronic-r1300/amtronic-r1300_user-instructions_2006422026.webp)
26
AMTRONIC R1300
Bistable distributor
Case N
°
1:
- ACTAIR 3 to 200, end-stops on closing
- ACTAIR NG 2 to 160, end-stops on closing
- DYNACTAIR 1.5 to 25, closing by air failure, end-stops on closing
- DYNACTAIR 50 and 100, opening by air failure, end-stops on opening
- DYNACTAIR NG 1 to 80, opening by air failure, end-stops on opening
EV1=0
EV2=0
EV1=1
EV2=0
EV1=0
EV2=1
Last command
Closed
Open
Case N
°
2:
- ACTAIR 3 to 200, end-stops on opening
- ACTAIR NG 2 to 160, end-stops on opening
- DYNACTAIR 1.5 to 25, opening by air failure, end-stops on opening
- DYNACTAIR 50 and 100, closing by air failure, end-stops on closing
- DYNACTAIR NG 1 to 80, closing by air failure, end-stops on closing
EV1=0
EV2=0
EV1=1
EV2=0
EV1=0
EV2=1
Last command
Open
Closed
4/3 distributor
Case N
°
1:
- ACTAIR 3 to 200, end-stops on closing
- ACTAIR NG 2 to 160, end-stops on closing
- DYNACTAIR 1.5 to 25, closing by air failure, end-stops on closing
- DYNACTAIR 50 and 100, opening by air failure, end-stops on opening
- DYNACTAIR NG 1 to 80, opening by air failure, end-stops on opening
Safety position on loss of
electrical supply
EV1=0
EV2=0
EV1=1
EV2=0
EV1=0
EV2=1
STOP
(stays in position)
STOP
(stays in position)
Closed
Open
Closed
Emergency manual controls not available
Open
Case N
°
2:
- ACTAIR 3 to 200, end-stops on opening
- ACTAIR NG 2 to 160, end-stops on opening
- DYNACTAIR 1.5 to 25, opening by air failure, end-stops on opening
- DYNACTAIR 50 and 100, closing by air failure, end-stops on closing
- DYNACTAIR NG 1 to 80, closing by air failure, end-stops on closing
Safety position on loss of
electrical supply
EV1=0
EV2=0
EV1=1
EV2=0
EV1=0
EV2=1
STOP
(stays in position)
STOP
(stays in position)
Open
Closed
Closed
Emergency manual controls not available
Open
Warnings
After using the emergency controls, remember to return the 2 controls to
position 0.
If you do not, the solenoid valve electrical controls will be inactive.
CAUTION!
Summary of Contents for AMTRONIC R1300
Page 2: ...2 AMTRONIC R1300...
Page 21: ...AMTRONIC R1300 21 VI 4 Angle sensor connection option...
Page 34: ...34 AMTRONIC R1300...
Page 35: ...35 AMTRONIC R1300...