X - Operating faults - Causes and solutions
Operating faults
Causes
Corrections
When the valve is closed, limit does not
change condition.
- The closure detection cam is positioned
incorrectly.
- Adjust the cam position.
When the valve is open, limit does not
change condition.
- The opening detection cam is positioned
incorrectly.
- Adjust the cam position.
One or more solenoid valves are activated
but the actuator does not move.
- No air supply
- Air pressure too high (P > 8 bar).
- Air pressure too low (P < 3 bar).
- Valve blocked
- Actuator blocked or destroyed
- Distributor obstructed by impurities
- Check the pneumatic supply.
- Check and restore pressure P.
- Check and restore pressure P.
- Check the freedom of movement of the
valve.
- Change the actuator.
- Change the inlet filter.
Operating time too long.
- Brake adjustment too long.
- Air pressure too high (P > 8 bar).
- Air pressure too low (P < 3 bar).
- Unscrew the brakes (operating
time adjustment)
- Check and restore pressure P.
- Check and restore pressure P.