AMTRONIC R1300
IX - Position recopy (option)
Adjustment of 0% and 100%
1 -
Using the 2 jumpers, select the feedback position operating mode:
4-- 20 mA
(4mA
closed position; 20 mA
open position) or
20- 4 mA
(20mA
closed position; 4 mA
open position)
Fonction 4
-
20 mA
(4mA
closed position; 20 mA
open position)
2 - Position the valve in
the closed position
3 - Adjust the potentiometer
0%
until the feedback loop gives a reading of
4 mA
4 - Position the valve in
the open position
5 - Adjust the potentiometer
100%
until the feedback loop gives a reading of
20 mA
6 - Repeat from
step 2
until the desired setting is achieved.
Fonction 20
-
4 mA
(20mA
closed position ; 4 mA
open position)
2 - Position the valve in
the open position
3 - Adjust the potentiometer
0%
until the feedback loop gives a reading of
4 mA
4 - Position the valve in
the closed position
5 - Adjust the potentiometer
100%
until the feedback loop gives a reading of
20 mA
6 - Repeat from
step 2
until the desired setting is achieved.