I -- 1 General
The AMTRONIC is especially suited to any
¼
turn VDI/VDE 3845 pneumatic actuator in particular the ACTAIR 3 to 200
series and DYNACTAIR 1.5 to 100 thanks to direct pneumatic distribution (without piping).
Command control functions
All versions of this box include the following electrical and pneumatic functions:
- On/off position detection using switches or proximity detectors,
- Pneumatic distribution by built in electro distributor (4 ports/2 positions or 4/ports/3 positions),
- Adjustment of open and close operating time, by air flow limiter on the exhaust.
Different options can be mounted on the unit and are included in this notice.
I - 2 Technical characteristics
Environment
Standard protection class
IP 67 according to EN 60529
Electromagnetic Compatibility
Complies with European directive CEM 2004/108/EC in accordance with NF
EN 61000- 6- 2 and NF EN 61000- 6- 4
Climatic class
- Storage temperature: - 30
°
C to + 80
°
C
- Working temperature: - 20
°
C to + 80
°
C
Vibrations
- According to IEC 68- 2- 6 Test Fc
Box
Material
PC 20% Fiberglass
Position signaling
By visible pointer on the cover
Pneumatic connection
2 times 1/4” gas
Electric connection
- by 2 M20 metallic or plastic cable glands for cable ø 6 to 12 mm,
- by 1 M12 5 pin female connector and a male connector
- by 2 Quick- On connectors
Internal connectors
- Length to be stripped : 7 mm
- Cross- section of rigid or flexible conductor: 0.14mm
2
to 1.5 mm
2
- Cross- section of flexible conductor with end connector without insulating
entry cone: 0.25 mm
2
to 1.5 mm
2
- Cross- section of flexible conductor with end connector with insulating
entry cone: 0.25 mm
2
to 0.5 mm
2
Weight
1,70 Kg
Pneumatic distribution
Pressure connection
Port 1/4” gas marked ”P” equipped with an internal filter
Exhaust connection
Port 1/4” gas marked ”E” equipped with a silencer or connectable to exhaust
network
Operating pressure
3 to 8 bar (44 to 115 psi)
Filtration level
ISO 8573-1 (2001) classe 7 (< 40
m)
Dew point
ISO 8573-1 (2001) classe 5 (<7
°
C and in all cases <5
°
C at ambient temperature)
Lubrication
ISO 8573-1 (1991) classe 5 (< 25mg/m
3
)
Maximum flow rate
400 Nl/min
Consumption when idle
none
Dimensions (mm)
F
153
97
View from F
51
122
69