AMTRONIC R1300
VIII - Position detection
Adjusting limit switches or contacts
The cams are preset in the factory. However, it is possible to adjust their positions, in particular if the actuator mechanical
stops are modified.
1 - Open the unit housing to access cam adjustment.
Unscrew the 4 TORX screws (T20) from the cover.
Tightening torque: 2 Nm
2 - Move the positioner to the end position (O or C).
3 - Remove the position pointer.
4 - Loosen the central screw of the cam (Torx screwdriver T20).
5 - Adjust triggering of the required contact by turning the coloured screw corresponding to the colour of the cam to be
adjusted (Red: closing; green: opening).
6 - Proceed in the same manner with the opposite contact (from step 2).
7 - Each cam is set independently and has no impact on the setting of the other cams.
8 - When the settings are finished, tighten the central screw of the cam moderately to lock the settings.