Part 2: Overview of display values and settings
Expert
area
45
DAY 1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
VT 25 25 25 55 55 55 55 25 40 55 55 55 55 55 55 55 55 55 55 40 25 --- --- --- --- --- --- ---
=>
SCREED PROGR (Program setting)
Ä
=> Screed program;
Ç
Select day;
Ä
=> Activate adjustment date;
Ç
Set flow temperature;
Ä
=> Save setting;
Ç
Select next day or exit screed program using "RETURN" +
Ä
.
Installation
Designation Value
range
Default
SCREED
00, 01 (OFF/ON) 00 = OFF
SCREED PROGR See explanation!
RETURN
Exit level using
Ä
!
Start day is not included:
The screed program starts with the "Day 1"
temperature setting and switches to "Day 1" at
00.00 hrs and then to the next day at 00.00 hrs and
so on. The current day is marked with an "x" in the
"SCREED PROGR" program.
!
After the function has been cancelled/terminated the
controller continues heating using the set operating
mode. If no heating is required, set the operating
mode to
i
= Standby / OFF.
Screed program
SCREED
(activation of screed drying process)
The screed program can be used for function heating in
accordance and for heating freshly laid screed ready for
flooring.
!
Screed drying can only be carried out for mixer
circuits.
After starting, the program runs through the set flow
temperatures. The integrated mixer circuits control to the
set flow temperature. The boiler provides this temperature
irrespective of the operating mode that has been selected.
This is marked in the standard display by the entry
"SCREED" and a display of the current flow temperature.
The freely adjustable program runs for a maximum of
28 days. The flow temperatures can be set to a value of
between 10°C and 60°C for each day. The entry "----"
stops the program (also during operation for the following
day).