Part 2: Overview of display values and settings
Expert
area
35
Installation
Designation Value
range
Default
IV
V-CURVE
00 - 11
00
CURVE 11-U1
0,00V – 10,00V
4,00V
CURVE 11-U2
0,00V – 10,00V
0,10V
CURVE 11-T1
00°C - 120°C
20°C
CURVE 11-T2
00°C - 120°C
90°C
CURVE 11-UO
0,00V – 10,00V
5,00V
See following pages for continuation
Table of voltage curves that can be chosen
No. U1 U2 T1 T2 UA
0 2,0
10,0
0 90 2,0
1 2.5 0.3 38 80 5,0
2 2.5 0.3 38 75 5,0
3 2.5 0.3 38 45 5,0
4 4.0 0.1 20 85 5,0
5 4.0 0.1 20 75 5,0
6 4.0 0.1 20 55 5,0
7 4.0 0.1 30 87 5,0
8 4.0 0.1 38 87 5,0
9 4.0 0.1 38 73 5,0
10 4.0 0.1 38 53 5,0
11 4.0 0.1 20 90 5,0
0-10 V Function
If the controller assigns the HS with the set temperature
through a voltage input, the 0-10V output on the controller
can be adjusted using the following parameters on the
voltage input of the HS.
If the 0-10V input of the controller is used for a temperature
requirement, the evaluation of the current signal is defined
using the same parameters.
V-CURVE (only for 0-10V input/output)
One of the defined voltage curves or free-definition curve
11 can be selected here for configuring the voltage input
and the voltage output.
CURVE 11-xx
Using parameters U1, U2, T1, T2 and UO, a special
voltage curve can be defined.
U = Voltage, T = Temperature, UO = HS OFF
U1, T1 => Point 1 on the voltage curve
U2, T2 => Point 2 on the voltage curve
The line between these limit points defines the voltage
curve.
UO => Starting with this voltage, HS = OFF
(Must lie outside of the valid voltage values)