Part 2: Overview of display values and settings
Expert
area
33
Expert area
These settings can only be changed if the code no. is
entered (see page 16).
E
If these values are set incorrectly, they may cause
malfunctions or damage to the system.
INSTALLATION
Designation Value
range
Default
IV
CODE-NO
0000 - 9999
Entry
->CODE-NO Adjustment 0000
BUS-ID HS
----, 01 - 08
----
BUS ID 1
(00), 01-15
01
BUS ID 2
(00), 01-15
02
AF SUPPLY
00.01 (Off/On)
01 = ON
BUS TERMIN
00, 01
01
EBUS SUPPLY
00.01 (Off/On)
01 = ON
TIME MASTER
00, 01 (OFF/ON) 00 = OFF
MAX T-HS1 or
MAX T-HEADER
30°C - 110°C
85°C
MIN T-HS1 or
MIN T-HEADER
10°C - 80°C
40°C
MAX T-HS2
30°C - 110°C
85°C
MIN T-HS2
10°C - 80°C
40°C
See following pages for continuation
CODE-NO
Entering the code number (see page 16) allows all of the
expert settings to be modified => including the code
number itself (first parameter)
(
Ç
on right => CODE-NO 0000
Ä
=>
Ç
1st digit
Ä
=>
Ç
2nd digit
Ä
=>
Ç
3rd digit
Ä
=>
Ç
4th digit
Ä
=>
Ç
)
BUS-ID HS (- - - -)
(not an option in all models)
The controller will be used as cascade with setting "01-08".
The heating circuits are then not available anymore.
BUS ID 1 / 2 (Heat circuit number)
The heating circuits are sequentially numbered starting
with "01". heating circuit numbers must not be assigned
twice. For replacement controllers however, please enter
exactly the same heating circuit numbers as the replaced
controller.
AF SUPPLY (Outdoor sensor power supply)
Switching off the power supply to the outdoor sensor.
Switching off allows up to 5 controllers to be operated with
a single outdoor sensor. The power supply must only be
switched on if there is one controller per sensor = "01".
BUS TERMIN (Bus terminating resistor)
The bus terminating resistor must be available once in the
bus system (HS controller or cascade controller).
When installing with a CoCo, set 1 to „00“.