User Area
Part 2: Overview of display values and settings
24
Hot water
Designation Value
range
Default IV
1X DHW
00, 01 (OFF/ON)
00 = OFF
T-DHW 1 DES 10°C - 70°C
60°C
T-DHW 2 DES 10°C - 70°C
60°C
T-DHW 3 DES 10°C - 70°C
60°C
BOB-VALUE
0K – 70K
0 K
CIRCL-P-DHW 00, 01 (OFF/ON)
00 = OFF
ANTILEGION
00, 01 (OFF/ON)
00 = OFF
RETURN
Exit level using
Ä
Hot water short time heating function
ANTILEGION = 01 => Every 20th time that heating takes
place or once per week on Saturday at 01:00 hrs the
storage tank is heated up to 65°C.
It is possible to set up your own hot water short time
heating function using the third hot water enable facility.
1X DHW (1x Hot water)
01 => The storage tank is enabled for charging
(e.g. for showering outside hot water times).
Charging starts when the temperature falls below
"temperature setting 1" by the switching hysteresis. After
charging, the value is automatically set to "00“ .
T-DHW 1-3 DES (Hot water temperature setting)
Required hot water temperature setting
T-DHW 1 DES => used in first enable time,
T-DHW 2 DES => used in second enable time ,
T-DHW 3 DES => used in third enable time of hot water
program.
Special application – flow heater
Without storage tank sensor connection, this function is
available for external boilers with bus connection.
T-DHW 1 => in operation 24 hours
BOB-VALUE (Operation Without Burner)
Energy saving function for solar or solid fuel integration
For settings
> "0"
the burner is not activated for hot water
preparation until the hot water temperature has dropped
below the temperature setting by the set value + the
switching hysteresis.
!
Alternative external energy sources with a bus
connection may affect this function (e.g. SD3-Can).
CIRCL-P-DHW (Circulation with hot water)
01 => The circulation pump runs when the hot water is
enabled, but the circulation program is disabled.
ANTILEGION (Hot water short time heating function)
01 => Activation of hot water short time heating function