Remote controls
Part 4:Appendix
60
DCF receiver
Electrical connection: Connector VII; Terminal 1,2
The controller can evaluate a eBUS DCF receiver on the
eBUS FA-Terminals.
If the DCF receiver is connected, the controller time is
updated as soon as the DCF transmits a valid time on the
BUS.
If the time has not been corrected after max. 10 min, select
a different place of installation for the DCF (e.g. another
wall - not in proximity to TV devices, monitors or dimmers).
PC
All system-specific parameters can be set and interrogated
using the
C
omfort
S
oft
parameterisation software. The
parameters can be saved, displayed graphically and
evaluated on the PC at predefined intervals. T connect to a
PC you need the optical adapter or CoCo PC active, which
also supports the sending of error messages by SMS and
the remote interrogation of controller data.
Telephone switch
The heating system can be switched to Heating mode
h
with a telephone switch. The connection terminals of the
controller for the remote control FBR (see connection
diagram) are used for installation. As soon as a short
circuit between terminal 3 of the FBR and ground (FBR
terminal 2) is detected, the assigned heating circuit is
switched to heating mode. Additionally the hot water
preparation is activated (only for controllers with hot water
preparation). When the short-circuit is eliminated, the
controller once again heats on the basis of the set heating
program.
E
If the heating circuit is controlled remotely by an
operating module, the telephone switch must be
connected at the operating module.