6
OPERATION
54
WATERFLUX 3070
www.krohne.com
06/2016 - 4004999701 - MA WATERFLUX 3070 - R01 en
6.3.7 Status output
30
Pulse output C
0 = Status output (default)
Sets status output 1 as status output
(select 0) or as pulse output (select 1,
2 or 3).
1 = Forward counter
2 = Reverse counter
3 = Net forward volume
31
Pulse output C:
unit of volume
00 = Litre (l)
01 = Cubic meter (m
3
) (default)
02 = Gallon (gal)
03 = Imperial gallon (i.gal)
04 = Cubic feet (ft
3
)
05 = Acre feet (a-ft)
06 = Acre inch (a-in)
32
Pulse output C:
pulse width
5 = 5 ms (default)
A small pulse width means a lower
energy consumption of the battery.
10 = 10 ms
20 = 20 ms
50 = 50 ms
100 = 100 ms
200 = 200 ms
33
Pulse output C:
pulse value
00100 = litre
Value to set in unit of volume per
pulse.
Unit and format are determined by
setting menu item 31
00.100 (default) = m
3
/ pulse
0010.0 = gallon
0010.0 = imp. gallon
001.00 = ft
3
.00100 = a-inch
.00100 = a-ft
0.1000 = m
3
/ pulse
When menu item A2 is set on 1
No.
Function
Options
Description
No.
Function
Options
Description
40
Status output 1:
Self check
0 = Off (default)
1 = On
41
Status output 1:
Battery pre warning
0 = Off (default)
Active in case of low battery
(remaining capacity < 10%).
1 = On
42
Status output 1:
Battery final warning
0 = Off (default)
Active in case of very low battery
(remaining capacity < 1%).
1 = On
43
Status output 1:
Empty pipe
0 =Off (default)
Active in case of empty pipe
detection.
1 = On