2.3 FORMAT
Format for transmitting Measured values or Error messages is as follows :
If there are no Fatal Errors detected by 5090(I) :
:QV<
QVval
><sp><sp><
QVunits
><sp><sp>
:QN<
QNval
><sp><sp><
QNunits
><sp><sp>
:QM<
QMval
><sp><sp><
QMunits
><sp><sp>
:TV<
TVval
><sp><sp><
TVunits
><sp><sp>
:TN<
TNval
><sp><sp><
TNunits
><sp><sp>
:TM<
TMval
><sp><sp><
TMunits
><sp><sp>
:PR<
PRval
><sp><sp><
PRunits
><sp><sp>
:TR<
TRval
><sp><sp><
TRunits
><sp><sp>
:VE<
VEval
><sp><sp><
VEunits
><sp><sp>
:FR<
FRval
><sp><sp><
FRunits
><sp><sp>
:TP<
TPval
><sp><sp><
TPunits
><sp><sp>
:TE<
TEval
><sp><sp><
TEunits
><sp><sp>
:QF<
QFval
><sp><sp><
QFunits
><sp><sp>
:XT<
XTval
><sp><sp><
XTunits
><sp><sp>
:XP<
XPval
><sp><sp><
XPunits
><sp><sp>
:NP<
NPva
l><sp><sp><
NPunits
><sp><sp>
:NE<
NEval
><sp><sp><
NEunits
><sp><sp>
:H<ID>E# nn Err#<sp><sp>
:m<
mesg
m><cr><lf>
If there are Fatal Errors detected by 5090(I) then measurement is not made and transmitted :
:FEFATAL.ERROR<cr><lf>
:H<ID>E# nn Err#<sp><sp>
:<mesg m><cr><lf>
where,
QVval
Numeric value of measured volumetric flowrate.
QVunit
Unit of the volumetric flowrate value.
QNval
Numeric value of measured normalised flowrate.
QNunit
Unit of the normalised flowrate value.
QMval
Numeric value of measured mass flowrate.
QMunit
Unit of the mass flowrate value.
TVval
Numeric value of computed totalised volumetric flow.
TVunit
Unit of the totalised volumetric flow value
TNval
Numeric value of computed totalised normalised flow.
TNunit
Unit of the totalised normalised flow value
TMval
Numeric value of computed totalised mass flow.
TMunit
Unit of the totalised mass flow value
PRval
Numeric value of the operating pressure.
PRunit
Unit of the operating pressure
TRval
Numeric value of operating temperature.
TRunit
Unit of the operating Temperature.
VEval
Numeric value of flow velocity.
VEunit
Unit of the flow velocity.
FRval
Numeric value of measured vortex frequency
FRunit
Unit of measured vortex frequency
TPval
Numeric value of computed thermal power
TPunit
Unit of thermal power
TEval
Numeric value of computed thermal energy
TEunit
Unit of thermal energy
QFval
Numeric value of computed FAD
QFunit
Unit of FAD
XT val
Numeric value of measured external temperature
22