OPERATION
6
81
OPTIFLEX 1300 C
www.krohne.com
01/2008 • 4000172301 - HB OPTIFLEX 1300 R02 en
Menu No. Function
Function description
Selection list
Default
C.2
I/O
For fieldbus. Not yet available.
C.3
output 1
(HART)
C.3.1
output
function
Select an output function to
scale the current values . This
is not displayed in the operator
mode.
1 solid/liquid: level, distance,
volume/mass, ullage volume;
2+ liquids: interface level,
interface distance, interface
volume, layer or layer volume
level
C.3.2
4 mA
setting
This gives a measurement
value to 4 mA
min.-max: 0
…
20 mA setting
1
0 m / 0 ft
C.3.3
20 mA
setting
This gives a measurement
value to 20 mA
min.-max:
2
depends on
the output
function
C.3.4
output
range
Sets the effective range of
output 1 either with or without
over-run
min.-max: 3.8
…
20.5 mA
(NAMUR), 4
…
20 mA
4
…
20 mA
C.3.5
error
handling
This sets the behaviour of
current output 1 if an error
occurs. Hold
Hold
Hold
Hold means that the
output current stays at the
value where the error occurred.
Hold
Hold
Hold
Hold is not available if
3.8
…
20.5 mA (NAMUR) is the
output range.
3.6 mA, 22 mA, Hold
22 mA
error
handling
delay
The time after which the
instrument shows there is a
measurement error.
min.-max: 0
…
900 seconds
60 seconds
C.3.6
HART
address
Any HART
®
address greater
than 0 will activate HART
®
multidrop mode. Current
output stays constant at 4 mA.
min.-max: 0
…
15
0
C.4
output 2
(passive)
C.4.1
output
function
Select an output function to
scale the current values . This
is not displayed in the operator
mode.
1 solid/liquid: level, distance,
volume/mass, ullage volume;
2+ liquids: interface level,
interface distance, interface
volume, layer or layer volume
level
C.4.2
4 mA
setting
This gives a measurement
value to 4 mA
min.-max: 0
…
20 mA setting
1
0 m / 0 ft
C.4.3
20 mA
setting
This gives a measurement
value to 20 mA
2
depends on
the output
function
C.4.4
output
range
Sets the effective range of
output 2 either with or without
over-run
min.-max: 3.8
…
20.5 mA
(NAMUR), 4
…
20 mA
4
…
20 mA
C.4.5
error
handling
This sets the behaviour of
current output 2 if an error
occurs. Hold
Hold
Hold
Hold means that the
output current stays at the
value where the error occurred.
Hold
Hold
Hold
Hold is not available if
3.8
…
20.5 mA (NAMUR) is the
output range.
3.6 mA, 22 mA, Hold
22 mA
HB_OPTIFLEX1300_EN_D4_080428.book Page 81 Tuesday, April 29, 2008 2:47 PM