OPERATION
6
73
OPTIFLEX 1300 C
www.krohne.com
01/2008 • 4000172301 - HB OPTIFLEX 1300 R02 en
Menu No. Step
Function
Function description
Selection list
Default
A.1.5
outputs
Follow this procedure to
describe the output
characteristics.
-
1
output 1: function
Select an output
function to scale the
current values . This is
not displayed in the
operator mode.
1 solid/liquid: level,
distance, volume
(mass), ullage volume;
2+ liquids: interface
level, interface
distance, interface
volume, layer, layer
volume
level
2
output 1: 4 mA
setting
This assigns a
measurement value to
4 mA.
min.-max: 0
…
20 m /
0
…
65.62 ft
0 m / 0 ft
3
output 1: 20 mA
setting
This assigns a
measurement value to
20 mA.
min.-max: 0
…
90 m /
0
…
295.29 ft
depends
on the
output
function
5
output 1: output
range
This sets the effective
range of output 1 with or
without over-run.
3.8
…
20.5 mA
(NAMUR), 4
…
20 mA
4
…
20 mA
6
output 1: error
handling
This sets the behaviour
of current output 1 if an
error occurs. Hold
Hold
Hold
Hold
means that the output
current stays at the
value where the error
occurred. Hold
Hold
Hold
Hold is not
available if 3.8
…
20.5 mA
(NAMUR) is the output
range.
3.6 mA, 22 mA, Hold
22 mA
7
output 1: HART
®
address
Any HART
®
address
greater than 0 will
activate HART
®
multidrop mode.
Current output stays
constant at 4 mA.
min.-max: 0
…
15
0
8
output 2: function
5
Select an output
function to scale the
current values . This is
not displayed in the
operator mode.
1 liquid: level,
distance, volume
(mass), ullage volume;
2+ liquids: interface
level, interface
distance, interface
volume, layer, layer
volume
interface
level
9
output 2: 4 mA
setting
5
This assigns a
measurement value to
4 mA.
min.-max: 0
…
20 m /
0
…
65.62 ft
0 m / 0 ft
10
output 2: 20 mA
setting
5
This assigns a
measurement value to
20 mA.
min.-max: 0
…
90 m /
0
…
295.29 ft
depends
on the
output
function
11
output 2: output
range
5
This sets the effective
range of output 2 with or
without over-run.
3.8
…
20.5 mA
(NAMUR), 4
…
20 mA
4
…
20 mA
HB_OPTIFLEX1300_EN_D4_080428.book Page 73 Tuesday, April 29, 2008 2:47 PM