3
INSTALLATION
28
OPTIFLEX 1300 C
www.krohne.com
01/2008 • 4000172301 - HB OPTIFLEX 1300 R02 en
3.6 Installation recommendations for liquids
3.6.1 General requirements
Figure 3-18:
Installation recommendations for liquids
1
h
≤
d, where h is the height of the tank nozzle and d is its diameter.
2
Make sure that the probe does not touch the nozzle. Attach the probe if the liquid is turbulent.
3
The electromagnetic (EM) field generated by the instrument. It has a radius of R
min
. Make sure that the EM field is
clear of objects and product flow. Refer to the table that follows.
4
If there are too many objects in the tank, install a bypass chamber or stilling well.
5
Keep the probe straight.
6
Empty space is not necessary for coaxial probes. Refer to the table that follows.
7
Empty space necessary for double probes. Refer to the table that follows.
8
Empty space necessary for single probes. Refer to the table that follows.
h
d
8
NOTE!
If your instrument has a coaxial probe, you can ignore these installation recommendations.
CAUTION!
Install coaxial probes in clean liquids that are not too viscous.
HB_OPTIFLEX1300_EN_D4_080428.book Page 28 Tuesday, April 29, 2008 2:47 PM