OPERATION
6
93
OPTIFLEX 1300 C
www.krohne.com
01/2008 • 4000172301 - HB OPTIFLEX 1300 R02 en
How to adjust the distance value to make the instrument measure level correctly
•
Go to the signal screen in operator mode. For more data, refer to
Operator mode
on page 60.
•
Press >>>> one time to move the cursor right to select the level signal
1
.
•
Make a note of the distance value on the signal screen.
•
Press
^
^
^
^
for three seconds.
i
The program mode screen is displayed.
•
Move the cursor to Supervisor
Supervisor
Supervisor
Supervisor and press
^
^
^
^
2
.
i
Type in the supervisor password, if this is necessary. For more data, refer to
How to get
access to the supervisor mode
on page 63.
•
Type in the distance value
3
.
i
The selected signal is the level signal.
•
Press
^
^
^
^
to accept your new value or press > and at the same time to reject it.
i
The display goes back to the signal screen.
How to adjust the interface distance value to make the instrument measure interface correctly
(instruments for interface measurement only).
•
Go to the signal screen in operator mode. For more data, refer to
Operator mode
on page 60.
•
Press >>>> 2 times to move the cursor right to select the interface signal.
•
Make a note of the distance value on the signal screen.
•
Press
^
^
^
^
for three seconds.
i
The program mode screen is displayed.
•
Select Supervisor
Supervisor
Supervisor
Supervisor and press
^
^
^
^
2
.
i
Type in the supervisor password, if this is necessary.
•
Type in the new interface distance value
3
.
i
The selected signal is the interface signal.
•
Press
^
^
^
^
to accept your new value or press >>>> and at the same time to reject it.
i
The display goes back to the signal screen.
INFORMATION!
If the instrument continues to select the parasite signal for level or interface measurement, use
the snapshot function to filter the signal. For more data, refer to How to use the snapshot
function to filter parasite signals that do not move
on page 97. If you cannot find the correct
signal on the signal screen, contact the supplier.
HB_OPTIFLEX1300_EN_D4_080428.book Page 93 Tuesday, April 29, 2008 2:47 PM