5-29
Accessory Troubleshooting
TP-5672 11/95
Use the following table to find the troubleshooting
flowchart for Option DD-18-J Current and Voltage
meters. Locate the DD-18-J accessory that is used on
your transfer switch in the left column. The flowchart
number for troubleshooting the voltmeter is in the center
column and the flowchart for troubleshooting the
ammeter is in the right column.
Options
with
DD-18-
Prefix
Voltmeter Troubleshooting
Ammeter
Troubleshooting
Flowchart
JA1
Figure 5-36
Figure 5-37
JA2
Figure 5-40 to Figure 5-45
Figure 5-46
JA3
Figure 5-36
Figure 5-37
JA4
Figure 5-38
Figure 5-39
JA5
Figure 5-40 to Figure 5-45
Figure 5-46
JA8
Figure 5-47 to Figure 5-52
Figure 5-46
JA9
Figure 5-47 to Figure 5-52
Figure 5-46
JA10
Figure 5-47 to Figure 5-52
Figure 5-46
JB1
Figure 5-36
Figure 5-37
JB2
Figure 5-40 to Figure 5-45
Figure 5-46
JB3
Figure 5-36
Figure 5-37
JB4
Figure 5-38
Figure 5-39
JB5
Figure 5-40 to Figure 5-45
Figure 5-46
JB6
Figure 5-47 to Figure 5-52
Figure 5-46
JB8
Figure 5-47 to Figure 5-52
Figure 5-46
JB9
Figure 5-47 to Figure 5-52
Figure 5-46
JB10
Figure 5-47 to Figure 5-52
Figure 5-46
JC1
Figure 5-36
Figure 5-37
JC2
Figure 5-40 to Figure 5-45
Figure 5-46
JC3
Figure 5-36
Figure 5-37
JC4
Figure 5-38
Figure 5-39
JC5
Figure 5-40 to Figure 5-45
Figure 5-46
JC8
Figure 5-47 to Figure 5-52
Figure 5-46
JC9
Figure 5-47 to Figure 5-52
Figure 5-46
JC10
Figure 5-47 to Figure 5-52
Figure 5-46
JD1
Figure 5-36
Figure 5-37
JD2
Figure 5-40 to Figure 5-45
Figure 5-46
JD3
Figure 5-36
Figure 5-37
JD4
Figure 5-38
Figure 5-39
Options
with
DD-18-
Prefix
Voltmeter Troubleshooting
Ammeter
Troubleshooting
Flowchart
JD5
Figure 5-40 to Figure 5-45
Figure 5-46
JD8
Figure 5-47 to Figure 5-52
Figure 5-46
JD9
Figure 5-47 to Figure 5-52
Figure 5-46
JD10
Figure 5-47 to Figure 5-52
Figure 5-46
JE1
Figure 5-36
Figure 5-37
JE2
Figure 5-40 to Figure 5-45
Figure 5-46
JE3
Figure 5-36
Figure 5-37
JE4
Figure 5-38
Figure 5-39
JE5
Figure 5-40 to Figure 5-45
Figure 5-46
JE8
Figure 5-47 to Figure 5-52
Figure 5-46
JE9
Figure 5-47 to Figure 5-52
Figure 5-46
JE10
Figure 5-47 to Figure 5-52
Figure 5-46
JF1
Figure 5-36
Figure 5-37
JF2
Figure 5-40 to Figure 5-45
Figure 5-46
JF3
Figure 5-36
Figure 5-37
JF4
Figure 5-38
Figure 5-39
JF5
Figure 5-40 to Figure 5-45
Figure 5-46
JF6
Figure 5-47 to Figure 5-52
Figure 5-46
JF8
Figure 5-47 to Figure 5-52
Figure 5-46
JF9
Figure 5-47 to Figure 5-52
Figure 5-46
JF10
Figure 5-47 to Figure 5-52
Figure 5-46
JG1
Figure 5-36
Figure 5-37
JG2
Figure 5-40 to Figure 5-45
Figure 5-46
JG3
Figure 5-36
Figure 5-37
JG4
Figure 5-38
Figure 5-39
JG5
Figure 5-40 to Figure 5-45
Figure 5-46
JG8
Figure 5-47 to Figure 5-52
Figure 5-46
JG9
Figure 5-47 to Figure 5-52
Figure 5-46
JG10
Figure 5-47 to Figure 5-52
Figure 5-46
JH1
Figure 5-36
Figure 5-37
JH2
Figure 5-40 to Figure 5-45
Figure 5-46
JH3
Figure 5-36
Figure 5-37
JH4
Figure 5-38
Figure 5-39
JH5
Figure 5-40 to Figure 5-45
Figure 5-46
JH6
Figure 5-47 to Figure 5-52
Figure 5-46
JH8
Figure 5-47 to Figure 5-52
Figure 5-46
JH9
Figure 5-47 to Figure 5-52
Figure 5-46
JH10
Figure 5-47 to Figure 5-52
Figure 5-46
Figure 5-34. Option DD-18, analog meters troubleshooting table
Option 18-JXXX,
analog meters
Turn ratio of transformer
JA1-5, JA8-10
30-5
JB1-6, JB8-10
75-5
JC1-5, JC8-10
100-5
JD1-5, JD8-10
150-5
JE1-5, JE8-10
300-5
JF1-6, JF8-10
400-5
JG1-5, JG8-10
600-5
JH1-5, JH8-10
800-5
Figure 5-35. Transformer Turn Ratio