4-32 Controller Troubleshooting
TP-5672 11/95
Time Delays
D
DD-100-B. This accessory allows all time delays to
be adjusted from 0 to 99 minutes.
Time Delay accessory DD-100-B increases all of the time
delays up to 99 minutes. The time delays are used for
transfer from normal to emergency, transfer from
emergency to normal, engine start, engine cooldown,
and load-shed sequence. The TIME DELAY jumper
must be installed on the main logic board to increase the
adjustable range of standard time delays up to
99 minutes. See Figure 4-15. To extend TDES time
delays an external 12-32 vdc power supply is required.
See Figure 4-15. Time delays are adjustable from either
the front panel keypad or from a remote computer. See
Figure 4-31 for a troubleshooting chart for this option.
No
Yes
No
No
Yes
Yes
Is the Time Delay jumper
installed in JP1 socket on
the logic board?
Replace logic board.
In Index 5 can TDES, TDEN,
TDOE, TDON and TDEC be
adjusted to 99 minutes?
Is there an external DC power
supply connected between
TB-DC1-29 and TD-DC1-32?
Option is working.
Yes
Connect an external DC power
supply between TB-DC1-29
and TD-DC1-32?
No
Install the Time Delay
jumper for on JP1 and
power down the controller
for 1 minute mininum.
In Index 11 are TD
Extended enabled?
Troubleshoot shunt-jumper
controlled options. See
Figure 4-18.
Figure 4-31. Troubleshooting— Extended time delays do not work