![Kohler M340+ Service And Parts Manual Download Page 101](http://html1.mh-extra.com/html/kohler/m340/m340_service-and-parts-manual_1989901101.webp)
5-40 Accessory Troubleshooting
TP-5672 11/95
NOTE: The ammeter reads load currents. The Source
selector switch must be in the NORM. NA-NB,
NB-NC, or NA-NC to read loads L1, L2, or L3.
Yes
No
No
Yes
Yes
No
Yes
Is the correct current for load L1
between terminal 12,13, or 14
and 21 of the source selector
switch? Refer to Figure 5-35 for
the proper turn ratio of the
current transformer.
Is the correct current for load L1 between
terminal 11 and 21 of the source selector
switch? Refer to Figure 5-35 for the
proper turn ratio of the current
transformer.
Are the leads from the current
transformer to the source selector
switch open or shorted?
Is the correct current for load L1
between the two terminals of the
ammeter?
Replace the source
selector switch.
Replace the leads from
the source selector
switch to the ammeter.
Replace the ammeter.
Replace the current
transformers.
Replace the leads from
the current transformer to
the source selector switch.
No
Figure 5-46. Troubleshooting— Option DD-18-J, Ammeter Does not read load for L1