5-7
Accessory Troubleshooting
TP-5672 11/95
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Is there continuity between
terminal TB-DC1-21 on the
power supply board and
terminal 7 of the test switch?
Place a jumper between terminals
TB-DC1-21 and TB-DC1-31 of the
power supply board. Does the
generator set start?
Refer to the Engine Start
Troubleshooting Flowchart.
Place a jumper between terminals
TB-DC1-21 to TB-DC1-22 of the power
supply board. Does the generator set
start when the test switch is in the
Engine Start position?
Is there continuity between
terminal TB-DC1-22 on the
power supply board and
terminal 9 of the test switch?
Replace the lead from
terminal TB-DC1-21 on
the power supply board
to the test switch.
Replace the lead from terminal
TB-DC1-22 on the power supply
board to the test switch.
Is there a jumper between
terminal 8 and terminal 9
of the test switch?
Replace the jumper between
terminal 8 and terminal 9 of
the test switch.
Install a jumper between
terminal 8 and terminal
9 of the test switch.
Is there continuity between
terminal TB-DC1-31 on the
power supply board and
terminal 10 of the test switch?
Replace the test switch.
Replace the lead from terminal
TB-DC1-31 on the power supply
board to the test switch.
Figure 5-7. Troubleshooting— Test switches, Option DD-07-D switch does not start the generator set when
in the engine start position