C-1
TP-5672 11/95
Commonly Used Accessories
Standard Accessories
D
Controller contains a CMOS microprocessor and nonvolatile
memory.
D
Microprocessor provides digital accuracy for time-delay,
source-transfer, and generator set exerciser intervals.
D
Controller is protected against EMI, voltage transients, ESD,
shock, vibration, and other hostile environments per U.S.A.,
Canadian, and IEC standards.
D
All printed circuit boards are conformal coated for
environmental protection.
D
Transfer switches with microprocessor logic have area
protection with override.
D
The normal source voltage is monitored across live lines of
single-phase switches, and all phases of normal source are
monitored line-to-line on three-phase switches.
D
The emergency source voltage and frequency are monitored
across one phase.
D
User-adjustable time delays include: Normal to Emergency
(TDNE), Engine Start (TDES), Emergency to Normal
(TDEN), Engine Cooldown (TDEC), Off to Emergency
(TDOE), and Off to Normal (TDON).
D
Each microprocessor-controlled transfer switch with a NEMA
type 1 enclosure has a front-accessible status panel.
D
An LCD display, touch key pad, and LED indicating lights
allow user interaction with the controller.
D
Generator set exercising intervals can be selected from
seven-day, fourteen-day, or calendar settings.
D
The test switch simulates a normal source power failure.
D
Ambienttemperaturerange:
Operating-20
_
Fto+150
_
F,
±
2% accuracy
Storage-60
_
Fto+220
_
F
D
Transfer Switch Humidity: 0 to 100% noncondensing,
operatingandstorage.
Shunt/Jumper-Controlled Accessories
-
DD-100-B
Extended Time Delay, adjustable from 0 to 99
minutes. Affects accessories TDNE, TDEN, TDES,
TDOE, TDON, TDEC, and Load sequence, if
ordered.
-
DD-23-C
No-load plant exerciser with override. Choice of
7-day, 14-day, or calendar-based exercise modes.
-
DD-34-A
Inphase monitor, both directions. Not available on
ATS withthe programmed transition function.
-
DD-34-J
Overvoltage sensing all phases,
over/underfrequency sensing for one phase on
normal source, and overvoltage/frequency sensing
one phase on emergency source
-
DD-34-Z
Phase rotation and anti-single-phasing protection.
Requires option DD-05-K for emergency source
sensing.
Optional Accessories
Source Monitors, Emergency
-
DD-05-K
Overfrequency sensing, 1-phase,
over/undervoltage sensing 3-phase, phase rotation
and anti-single-phasing protection
Two-Position Test Switch
-
DD-06-F
Momentary AUTO/TEST simulates normal power
failure, key-operated
Three-Position Test Switches
-
DD-06-N
Momentary TEST/AUTO/ENGINE START
-
DD-06-P
Momentary TEST/AUTO/ENGINE START,
key-operated
Four-Position Test Switch
-
DD-07-D
TEST/AUTO/OFF/ENGINE START
Time Delay Override Switch
-
DD-08-C
Time delay emergency-to-normal
-
DD-08-D
Time delay normal-to-emergency
Preferred source switch
-
DD-10-D
Two position switch for use with two generator
sets.
Auxiliary Contacts
-
DD-14-G
Ten-contact kit for remote indication. Contacts
rated 10 amps., 125 vac. Indicates contactor
positions, sources available, program mode, and
system alarm.
-
DD-14-H
Single-contact kit for remote indication, rated 10
amps., 120 vac, in normal contact position
-
DD-14-J
Indicates contactor in emergency position
-
DD-14-K
Indicates normal source present
-
DD-14-L
Indicates emergency source present
-
DD-14-M
Indicates ATS not in AUTO
-
DD-14-N
Indicates program switch not in OFF
-
DD-14-P
Indicates system alarm
-
DD-14-R
Load bank control
-
DD-14-S
Indicates contactor in off position
NOTE:
A maximum of two DD-14-H through DD-14-S may be
fitted to a transfer switch, either by themselves or in
addition to one DD-14-G
Auxiliary Contacts— Main Shaft Position. Dependent on
power switch.
-
DD-15-E
One additional closed on normal
-
DD-15-F
One additional closed on emergency
Meters
-
DD-18-G
Frequency meter, analog, fused
-
DD-18-J
Voltmeter and ammeter, analog, fused
Plant Exercisers
-
DD-23-D
Plant exerciser, load transfer with override. Choice
of 7-day, 14-day, or calendar-based modes.
-
DD-23-G
Plant exerciser, load/no-load transfer with
two-position selector switch and override. Choice
of 7-day, 14-day, or calendar-based modes.