![Kohler M340+ Service And Parts Manual Download Page 41](http://html1.mh-extra.com/html/kohler/m340/m340_service-and-parts-manual_1989901041.webp)
4-14 Controller Troubleshooting
TP-5672 11/95
Fault LED
TB-DC1-8
P2-7
P2-7
Main Logic Board
Power Supply Board
560449
Figure 4-9. Wiring Diagram— Fault #1 or Fault #2 message
Fault #1 Or Fault #2 Message
The external fault function can be used to identify a
problem with the emergency power system, or a support
device of the emergency power system. A dry relay
contact can be used to signal a fault, such as a Ten Relay
Dry Contact Kit, sold as an accessory with the generator
set.
NOTE: The contact kit must be a dry contact, the logic
controller supplies its own voltage source.
The fault messages are used to monitor accessory
components. A fault message appears on the LCD when
an accessory is grounding the pin to which it is
connected. See Figure 4-9.
1. If a FAULT #1 message appears on the LCD, check
TB-DC1-8.
a. If there is an accessory connected to TB-DC1-8,
disconnect the accessory. Press the RESET
MENU key. If the message disappears, the logic
board is performing correctly. The FAULT #1
message is caused by the connected accessory.
b. If there is not an accessory connected to
TB-DC1-8, remove power from the logic board
and disconnect the P2 ribbon cable connector
from the power supply board. Using an
ohmmeter, connect one test lead to P2-7 on the
power supply board. Connect the other test lead
to TB-DC1-34. If the resistance is low, replace
the power supply board. If the resistance is high,
replace the logic board assembly.
2. If a FAULT #2 message appears on the LCD, check
TB-DC1-11.
a. If there is an accessory connected to
TB-DC1-11, disconnect the accessory. If the
message disappears, then the logic board is
performing correctly.
b. If there is not an accessory connected to
TB-DC1-11, remove power from the logic board
and disconnect the P2 ribbon cable connector
from the power supply board. Using an
ohmmeter, connect one test lead to P2-8 on the
power supply board. Connect the other test lead
to TB-DC1-34. If the resistance is low, replace
the power supply board. If the resistance is high,
replace the logic board assembly.