B-4 Appendices
TP-5672 11/95
Pin
P1-J1 Contactor-transformer Pin Names
1
Normal Phase B.
2
Normal Phase C.
3
N/A
4
Normal contactor position auxiliary contact
common.
5
Normal Phase A.
6
N/A
7
N/A
8
Emergency contactor position auxiliary contact
common.
9
N/A
10
N/A
11
Engine start contact 3.
12
Normal contactor position auxiliary contact
normally open.
13
Emergency Phase C.
14
N/A
15
Engine start contact 4
16
Emergency contactor position auxiliary contact
normally open.
17
Emergency Phase B for sensing.
18
N/A
19
N/A
20
N/A
21
Emergency Phase A
22
N/A
23
Load Phase A
24
Load Phase C
Figure B-3. P1-J1 contactor to power supply board
harness pin numbers and pin names
Trip Point
Setting
Limits
Emergency
Source Factory
Settings
Overvoltage
Dropout
115%-135%
115%
Overvoltage
Pickup
110%-130%
110%
Undervoltage
Pickup
75%-100%
90%
Undervoltage
Dropout
70%-95%
85%
Overfrequency
Dropout
105%-135%
115%
Overfrequency
Pickup
100%-130%
110%
Underfrequency
Pickup
85%-100%
90%
Underfrequency
Dropout
80%-95%
85%
Figure B-4. Emergency source voltage trip point
setting limits and factory settings
Line Voltage
(Volts)
1/25 Of Line
Voltage
(Volts)
120
4.8
208
8.3
240
9.6
480
19.2
600
24.0
Figure B-5. 1/25 of the line voltage