TP-5867 11/02
56
Section 6 Component Testing and Adjustment
17. Disconnect the DVM leads from the oxygen
sensor.
18. Remove the oxygen sensor from the exhaust
manifold.
19. Apply a small amount of antiseize compound to
exhaust plug and reinstall the plug into the exhaust
manifold.
20. Check that the generator set master switch is in the
OFF position.
21. Reconnect the generator set engine starting
battery, negative (--) lead last.
22. Reconnect power to the battery charger, if
equipped.
6.11.6 Fuel Conversion, Multi-Fuel
Systems
Generator sets with multi-fuel systems are CARB- and
EPA-certified for both natural gas and LP vapor fuels.
The multi-fuel system allows conversion from natural
gas to LP vapor (or vice-versa) in the field while
maintaining emissions-standard compliance.
Two fuel connections on the fuel block allow field-
conversion between natural gas and LP vapor. The fuel
metering valves are factory-set and sealed to comply
with applicable emission standards and to provide the
best possible hot and cold starting.
Note:
Do not adjust the factory-sealed fuel-metering
adjustments on the fuel block.
Changing the
fuel-metering adjustments on these units may
violate federal or state laws.
The manufacturer ships the generator set with the fuel
system connected for natural gas. To convert to LP gas,
use the following procedure to move the fuel line from
the natural gas outlet port to the LP outlet port in the fuel
block (or from the LP outlet to the natural gas outlet to
convert from LP to natural gas). See Figure 6-30 for the
fuel block and fuel inlet locations.
OUT
IN
1
ADV-6600
1. Multi-fuel block
2. Fuel inlet, 1/2 in. NPT female
2
Figure 6-30
Multi-Fuel Generator Set Fuel Block
Location, Air Inlet Side
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working
on
the
generator
set.
Remove the negative (--) lead first
when
disconnecting
the
battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
WARNING
Disabling the generator set.
Accidental starting can
cause severe injury or death.
Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.
Summary of Contents for 11RMY
Page 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Page 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Page 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Page 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Page 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Page 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Page 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Page 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Page 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Page 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Page 96: ......
Page 97: ......