TP-5867 11/02
33
Section 5 Generator/Relay Controller Troubleshooting
Engine starts but
shuts down after 30 seconds
Engine runs but
cannot be stopped by
moving master switch
to OFF/RESET
position
Yes
Crank/disconnect
relay LED lit?
No
Yes
Check for 120 volts AC output from
stator 1-2 winding at V0 and V7. See
Section 9, Wiring Diagrams. Generator
set must be running while performing
this test.
Test
magnetic
pickup
operation
as
described in Section 7, Magnetic Pickup.
If specified voltage is present and
magnetic pickup tests good, replace
circuit board.
Note:
Allow a 60-second cooldown
between cranking attempts if the
set does not start.
Replace
circuit
board
Check condition/connections of master switch
Switch okay?
No
Yes
Repair/
replace
switch
Start/run relay
defective;replace
circuit board
B
Figure 5-3
Troubleshooting the Relay Controller Circuit Board (3 of 3)
Summary of Contents for 11RMY
Page 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Page 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Page 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Page 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Page 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Page 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Page 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Page 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Page 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Page 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Page 96: ......
Page 97: ......