TP-5867 11/02
46
Section 6 Component Testing and Adjustment
controller. Restart the generator set and verify that it
does not shut down. A successful restart indicates a
faulty LOP switch. Replace the switch.
High Engine Temperature (HET) Switch
Sound-enclosure models use a normally open high
engine temperature switch. See Section 1.6, Service
Views, for the switch location. Set the generator set
master switch to the OFF position and allow the
generator set to cool.
Disconnect the high engine
temperature switch and use an ohmmeter to check the
continuity from the switch center terminal (lead 37) to
ground.
The ohmmeter should show no reading,
indicating an open circuit. Any other reading indicates a
shorted switch.
Note:
The HET switch is located in the engine oil pan.
Drain the engine oil before removing the switch.
6.9 Electronic Governor
The governor system consists of an electronic
isochronous governor controller, an electromechanical
stepper motor (actuator), and a magnetic pickup. See
Section
9,
Wiring
Diagrams,
for
the
governor
connections.
6.9.1
Operation
The frequency of the alternator output is determined by
the speed of the engine. A two-pole alternator must be
driven at 3600 RPM to provide 60 Hertz. (A 50 Hz model
must be driven at 3000 RPM.) The engine speed is
maintained by an electronic governor system that
consists of a magnetic pickup, electric actuator (stepper
motor), and electronic governor controller.
The electronic governor controller is energized with a 12
VDC supply from the K25 start/run relay contacts.
The magnetic pick-up, which monitors the speed of the
flywheel ring gear, provides the speed reference signal
to the electronic control board.
The control board
provides regulated power to the bidirectional stepper
motor actuator, which is linked to the carburetor throttle
arm.
At cranking speed a properly adjusted pick-up should
produce a minimum of 1.75 VAC. The magnetic pick-up
air gap is factory-set to 1.02 mm (0.040 in.). Failure or
loss of the input speed signal from the magnetic pick-up
will result in a low or idle speed condition.
A potentiometer on the governor controller allows
adjustment of the engine speed within the 50/60Hz
range. See Section 6.9.3.
A gain adjustment may be required if an unstable
(hunting/surging) condition occurs. Adjusting the gain
may require readjustment of the engine speed. See
Section 6.9.3.
6.9.2
Initial Checks and Operation Test
The factory sets the electronic governor. Under normal
circumstances the electronic governor requires no
further adjustment. Verify that the governor stepper
motor moves smoothly and steadily during operation. If
the engine operates erratically check the following
connections and conditions
before
adjusting the
governor.
D
Verify that the electrical connections, including the
stepper motor and governor connector (inside the
generator set controller), are clean and tight.
D
Check the magnetic pickup connections. Poor
connections may cause an erratic signal. An erratic
signal causes the generator set to govern poorly but
not shut down.
D
Check the electrical ground connections. Provide a
good DC ground to the controller assembly and
governor circuit.
D
Verify that the battery connections are clean and tight.
D
Check for dirt buildup on the magnetic pickup. Metal
filings or caked-on dirt or grease decreases the output
signal of the magnetic pickup.
D
Check for a loose or worn stepper motor/throttle shaft
coupling.
D
Check
the
carburetor
for
dirt,
grime,
or
misadjustment.
Also, check the idle-adjustment
screw. The screw should not prevent the throttle plate
from closing completely.
Also, check the throttle
linkage for any binding, dirt, damage, or other visible
problems.
D
Check whether the positive voltage supply is
unstable or below 8 volts DC, causing the control unit
to function erratically.
D
Check for electronic governor faults. The fuel shutoff
solenoid deenergizes and the generator set shuts
down under the following conditions:
D
Closed throttle
D
Engine overspeed
D
Broken fuel shutoff solenoid lead
D
Lost DC power to governor assembly
D
Broken stepper motor leads (erratic performance)
D
Failed actuator linkage (erratic performance)
Summary of Contents for 11RMY
Page 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Page 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Page 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Page 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Page 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Page 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Page 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Page 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Page 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Page 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Page 96: ......
Page 97: ......