![Kohler 11RMY Service Manual Download Page 48](http://html1.mh-extra.com/html/kohler/11rmy/11rmy_service-manual_1989770048.webp)
TP-5867 11/02
38
Section 6 Component Testing and Adjustment
6.3.2
Voltage Regulator Adjustment
The factory sets the voltage regulator for correct
generator operation under a variety of load conditions.
Usually, the voltage regulator needs no further
adjustment. Adjust the regulator according to the
following procedure after voltage reconnection or if the
regulator has been tampered with or replaced.
The
voltage
adjustment
procedure
uses
three
potentiometers located on the voltage regulator. See
Figure 6-4 and Figure 6-7. The procedure also requires
a meter that can measure voltage and frequency.
Voltage
Adjustment
Potentiometer
Adjusts
generator output between 100 and 130 volts.
Stabilizer Potentiometer
Fine tunes regulator circuitry
to reduce light flicker.
Volts/Hz Potentiometer
Determines frequency (Hz) at
which generator output voltage begins to drop.
Note:
In applications requiring fine voltage adjustment,
connect a 10 kOhm, 1/2 watt minimum rheostat
(customer-provided) across terminals 33 and 66
on the PowerBoost
ä
IIIE voltage regulator. See
Figure 6-6. The rheostat provides a 5-volt
adjustment range.
+
--
4
3
33
44
2
1
55
GY R Y O W BK
66 44 3355 -- +
66
1
2 3 4
5
6
8
7
9
10
11
13
TP563277
4
3
33
12
1. Remote rheostat (customer-provided)
2. Voltage adjustment potentiometer
3. Stabilizer potentiometer
4. Volts/Hz potentiometer
5. Stator/rotor connections (for reference only)
6. Lead color
7. DC output
8. Main field (rotor)
9. 5-amp fuse
10. Sensing leads (33-44)
11. AC power input (auxiliary) lead (55)
12. Main leads (1--2, 3--4)
13. Stator
12
Figure 6-6
PowerBoost
ä
IIIE Voltage Regulator Test
and Adjustment Setup
A-358076
1
6
68
68
67
67
FP
FP
FN
FN
70
70
7N
7N
3
4
32
32
GRD
3
2
4
1. Voltage regulator
2. V/Hz potentiometer
3. Stabilizer potentiometer
4. Voltage adjustment potentiometer
5. Circuit breaker
6. Governor circuit board
5
Figure 6-7
Controller Top View, Typical
Hazardous voltage.
Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
are in place.
Moving rotor.
WARNING
Summary of Contents for 11RMY
Page 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Page 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Page 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Page 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Page 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Page 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Page 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Page 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Page 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Page 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Page 96: ......
Page 97: ......