TP-5867 11/02
48
Section 6 Component Testing and Adjustment
tp5867
Check the throttle linkage connection.
See step 1 and Figure 6-16.
Check for broken or loose wiring or con-
nections and other items in step 2.
Check stepper motor operation at startup.
Does it move to fully open and then move
to and stay in the fully closed position?
See step 3.
Check the magnetic pickup. See steps 4--6.
Check the stepper motor coils. See step 11.
Yes
No
Disconnect the magnetic pickup and check the stepper
motor operation again. See steps 7--9.
Replace the electronic governor. See step 12.
Check for voltage and a good ground connection at the
governor controller. See step 10.
Figure 6-18
Governor System Operation Test Procedure Summary
5. If the voltmeter displays less than 1.75 volts AC,
check the air gap as described in the following
steps before replacing the sensor. Verify that the
magnetic pickup air gap is 1.02 mm (0.040 in.).
Measure the air gap at 3 or 4 places to get an
accurate reading. See Figure 6-19.
a. Stop the generator set.
Remove housing
panels and the junction box as required to gain
access to the front of the engine.
b. Remove the engine blower housing.
c. Use a feeler gauge to check the gap. The gap
should be 1.02 mm (0.040 in.).
d. Adjust the air gap, if necessary, by loosening
the locknut and turning the pickup.
See
Figure 6-19.
e. Hold the pickup in position and retighten the
locknut.
f. Verify the magnetic pickup air gap after
tightening the locknut.
A-358000B-C
1
2
3
4
5
1. Ignition module
2. Air gap
3. Top of flywheel ring gear tooth
4. Lock nut
5. Magnetic pickup
Figure 6-19
Magnetic Pickup Air Gap
Summary of Contents for 11RMY
Page 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Page 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Page 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Page 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Page 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Page 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Page 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Page 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Page 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Page 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Page 96: ......
Page 97: ......