TP-5867 11/02
54
Section 6 Component Testing and Adjustment
IN
OUT
3
2
4
1
1. Secondary pressure regulator
2. Fuel metering valve (single-fuel models)
3. Inlet pressure check location (plug)
4. Fuel solenoid valve
5. Fuel lockoff
A-227531-C
TP-5868
1
5
Figure 6-27
Fuel Regulator and Valve
6.11.4 Fuel Conversion, Single-Fuel
Models
Do not change the fuel on emission-certified single-fuel
generator sets. The fuel systems on emission-certified
units are factory-set and sealed to meet EPA and
California emissions regulations.
Emission-certified
units bear a decal similar to the one shown in
Figure 6-28.
* Spark-Ignited Small Off-Road Engines
*
Figure 6-28
Emission-Certification Decal, Typical
Generator sets that do not have emission-certified
engines can be converted from natural gas to LP or
vice-versa in the field. Follow the procedure in Section
6.11.5 to adjust the fuel metering valve when changing
fuels. When switching from natural gas to LP gas or
vice-versa, verify that the engine speed meets
specifications.
The
electronic
governor
should
compensate for different types of fuel and maintain the
rated engine speed. If the engine speed is incorrect,
refer to Section 6.9, Electronic Governor, to make
adjustments.
6.11.5 Fuel Metering Valve Adjustment
Note:
Do not adjust the fuel metering valves on
emissions-certified generator sets.
The fuel system is factory-adjusted to comply with
applicable emission standards and to provide the best
possible hot and cold starting. The fuel metering valves
are sealed to discourage field adjustments. If the fuel
system requires adjustment, only trained, authorized
service technicians may adjust the fuel metering valves.
The adjustment procedure requires a digital volt meter
(DVM), oxygen sensor (A-345052) for the engine, and a
load bank capable of the rated kW for the fuel being
used. Always use an oxygen sensor when adjusting the
fuel metering valves.
Observe
the
following
safety
precautions
while
performing the procedure.
Summary of Contents for 11RMY
Page 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Page 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Page 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Page 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Page 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Page 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Page 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Page 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Page 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Page 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Page 96: ......
Page 97: ......