TP-5867 11/02
21
Section 3 Troubleshooting
Problem
Possible Cause
Corrective Action
Reference
No generator
output voltage
Defective stator (open, grounded, or
shorted windings)
Test and/or replace.
Section 6, Component
Testing and Adjustment
p
g
K1 relay (NC) contact open
Check continuity.
Section 4, Controller
Troubleshooting and 9,
Wiring Diagrams
Brushes sticking in holder
Check springs and alignment.
Section 6.6, Brushes
Rotor slip rings dirty or corroded
Check and/or service.
Section 6.6, Brushes
Worn brushes
Replace worn brushes.
Section 6.6, Brushes
Defective or misadjusted voltage
regulator
Excite (rotor) separately.
Section 6, Separate
Excitation, and 6.3.1, Voltage
Regulator Test
Low engine rpm
Check engine speed using a
tachometer or frequency meter.
Note:
Hz x 60 = rpm
(Example 57 x 60 = 3420 rpm)
—
No AC output
Circuit breaker open or defective, if
equipped
Reset breaker to ON position.
Check AC voltage on generator
side of circuit breaker.
Section 1.6, Service Views,
for location
Circuit breaker tripping because of
overload on generator set
Reduce load.
O/M
No battery voltage to voltage regulator
during cranking: (+) and (--) terminals
on regulator
Check for DC voltage at voltage
regulator terminals listed.
Sections 6.3, Voltage
Regulator, and 9, Wiring
Diagrams
Blown voltage regulator fuse
Replace fuse; if fuse blows again,
check voltage regulator and/or
stator auxiliary windings.
Sections 6.3, Voltage
Regulator, and 9, Wiring
Diagrams
Open wiring, terminal, or pin in buildup
circuit or voltage regulator circuit
Check continuity.
Sections 6.3, Voltage
Regulator, and 9, Wiring
Diagrams
Brushes sticking in brush holder or
broken brush spring
Check brush position and
condition.
Section 6.6, Brushes
Rotor slip rings dirty or corroded
Check slip ring condition.
Section 6.4, Main Field
(Rotor)
Defective rotor (grounded windings)
Check voltage and continuity.
Section 6.4, Main Field
(Rotor)
Defective stator (open, grounded, or
shorted windings)
Check voltage and continuity.
Section 6.5, Stator
Defective or misadjusted voltage
regulator
Excite rotor separately and check
for AC output. Readjust voltage
regulator.
Section 6.3, Voltage
Regulator
Defective K3 relay (field flashing) in
relay controller circuit board
Test/replace relay controller circuit
board.
Section 4, Controller
Troubleshooting
Summary of Contents for 11RMY
Page 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Page 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Page 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Page 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Page 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Page 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Page 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Page 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Page 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Page 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Page 96: ......
Page 97: ......