![KNX AQS/TH-UP Touch Installation And Adjustment Manual Download Page 9](http://html1.mh-extra.com/html/knx/aqs-th-up-touch/aqs-th-up-touch_installation-and-adjustment-manual_1981084009.webp)
7
Installation and commissioning
Sensor KNX AQS/TH-UP Touch
as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
The device may only be used as a fixed-site installation; that means only when
assembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.2. Installation position
The
Sensor KNX AQS/TH-UP Touch
is made for wall mounting in a socket
(Ø 60 mm, 42 mm deep).
May be installed and operated in dry interior rooms only.
Avoid condensation.
When selecting an installation location, please ensure that the measurement results
are affected as little as possible by external influences. Possible sources of interference
include:
•
Direct sunlight
•
Drafts from windows and doors
•
Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
•
Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
•
Connection lines and ducts which lead from warmer or colder areas to the
sensor
Measurement variations from permanent sources of interference can be corrected in
the ETS in order to ensure the specified accuracy of the sensor (offset).
To ensure a correct CO
2
measurement, the device must be installed in a windproof
socket.
Fig. 1: Sectional drawing.
The
Sensor KNX AQS/TH-UP Touch
fits into a standard
socket (Ø 60 mm, depth 42 mm).
The frame is not included!
Summary of Contents for AQS/TH-UP Touch