![KNX AQS/TH-UP Touch Installation And Adjustment Manual Download Page 63](http://html1.mh-extra.com/html/knx/aqs-th-up-touch/aqs-th-up-touch_installation-and-adjustment-manual_1981084063.webp)
61
Parameter setting
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
Dead man‘s switch:
Shutter
Standard:
Standard inverted
Comfort mode:
Dead man‘s switch:
Push button
down command
Release button
up command
Pushbutton function
• Up
• Down
• Up/Down
Control mode
• Standard
• Standard inverted
• Comfort mode
• Dead man‘s switch
Behaviour for button actuation (up): short = Stop | long = Up
Behaviour for button actuation (down): short = Stop | long = Down
Behaviour in case of button actuation (up/down): short = Stop | long = Up/Down
Time between short and long
in 0.1 seconds
0 ... 50; 10
Behaviour for button actuation (up): long = Stop | short = Up
Behaviour for button actuation (down): short = Stop | long = Down
Behaviour in case of button actuation (up/down): short = Stop | long = Up/Down
Time between short and long
in 0.1 seconds
0 ... 50; 10
Repeat the step command
for a long button press (only Up)
no • every 0,1 s • ... • every 0,5 s • ... • every
2 s
Button is pushed and
released before time 1 expired
held longer than time 1
released between time 1 and 1-2
released after time 1 +2
Stopp
Up | Down | Up/Down
Stop
no more stop
Time 1 (in 0,1 s)
0 ... 50; 4
Time 2 (in 0,1 s)
0 ... 50; 20
Push button
Up- | Down- | Up/Down command
Release button
Stop command