16
Transfer protocol
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
80
Humidity controller: Target value
(1:+ | 0:-)
Input
-WC-
[1.2]
DPT_Bool
1 Bit
81
Humidity controller: Control varia-
ble dehumidification (stage 1)
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
82
Humidity controller: Control varia-
ble dehumidification stage 2
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
83
Humidity controller: Control varia-
ble humidification
Output
R-CT
[5.1]
DPT_Scaling
1 Byte
84
Humidity controller: Dehumidifica-
tion 1 status (1=ON | 0=OFF)
Output
R-CT
[1.1]
DPT_Switch
1 Bit
85
Humidity controller: Dehumidifica-
tion 2 status (1=ON | 0=OFF)
Output
R-CT
[1.1]
DPT_Switch
1 Bit
86
Humidity controller: Humidification
status (1=ON | 0=OFF)
Output
R-CT
[1.1]
DPT_Switch
1 Bit
87
Dewpoint temperature
Output
R-CT
[9.1]
DPT_Value_Temp
2 Bytes
88
Coolant temp.: Threshold value
Output
R-CT
[9.1]
DPT_Value_Temp
2 Bytes
89
Coolant temp.: Actual value
Input
-WC-
[9.1]
DPT_Value_Temp
2 Bytes
90
Coolant temp.: Offset change (1:+ |
0:-)
Input
-WC-
[1.2]
DPT_Bool
1 Bit
91
Coolant temp.: Switching delay
from 0 to 1
Input
-WC-
[9.010]
DPT_Value_Time
2 Bytes
92
Coolant temp.: Switching delay
from 1 to 0
Input
-WC-
[9.010]
DPT_Value_Time
2 Bytes
93
Coolant temp.: Switching output
Output
R-CT
[1.1]
DPT_Switch
1 Bit
94
Coolant temp.: Switching output
block
Input
-WC-
[1.2]
DPT_Bool
1 Bit
95
Absolute humidity [g/kg]
Output
R-CT
[14.5]
DPT_Value_Ampli-
tude
4 Bytes
96
Absolute humidity [g/m³]
Output
R-CT
[14.17]
DPT_Value_Density
4 Bytes
97
Ambient climate status: 1 = com-
fortable | 0 = uncomfortable
Output
R-CT
[1.2]
DPT_Bool
1 Bit
98
Outside CO2 reading
Input
-WC-
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
99
Inside CO2 Internal reading
Output
R-CT
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
No Name
Function Flags Data Point Type
Size