Parameter setting
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
Setpoint value setting using parameters:
Set the setpoint value directly.
Setpoint value setting via communication object:
Enter, how the setpoint value will be received from the bus. Basically, a new value can
be received, or simply a command to increase or decrease.
During initial commissioning, a setpoint value must be defined which is valid until the
first communication of a new setpoint value. For units which have already been taken
into service, the last communicated setpoint value can be used. Basically, an air humid-
ity range is given in which the setpoint value can be changed (object value limit).
A set setpoint value will be retained until a new value or a change is transferred. The
current value is saved, so that it is retained in the event of a power supply failure and
will be available once the power supply is restored.
Ventilation control
Depending on the control mode, one and/or two setting sections for the ventilation
stages are displayed.
For two-stage ventilation, the setpoint value difference between the two stages must
be defined, i.e. the setpoint value which, when exceeded, triggers the switch to the 2nd
level.
Specified setpoint using
Parameter
• Communication objects
Target value in ppm
300…5000; 800
Threshold value setting using
Parameter •
Communication objects
The last communicated value should be
retained
• never
• after power supply restoration
• after power supply restoration and
programming
Start setpoint value in ppm
valid until first communication
(not upon saving the setpoint value after
programming)
300… 5000; 800
Object value limit (min) in 0.1°C
300…5000; 400
Object value limit (max) in 0.1°C
300…5000; 1500
Type of threshold value change
Absolute value • Increase/decrease
Increment in ppm
(upon increase/decrease change)
1 • 2 • 5 • ... • 20 • ... • 100 • 200
Target value difference between 1st and
2nd level in ppm
(for level 2 only)
100...2000; 400