Parameter setting
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
5.6.
Humidity measurement
Select (see
5.2.General settings
), whether a
malfunction object
is to be sent if the
sensor is faulty.
Use
Offsets
to adjust the readings to be sent.
The unit can calculate a
mixed value
from its own reading and an external value. Set
the mixed value calculation if desired. If an external portion is used, all of the following
settings (threshold values, etc.) are related to the overall reading.
The
minimum and maximum readings
can be saved and sent to the bus. Use the
„Reset humidity min/max value“ object to reset the values to the current readings. The
values are not retained after a reset.
5.7.
Humidity threshold values
Activate the required air humidity threshold values. The menus for setting the thresh-
old values are displayed.
When blocked, the control variable shall
• not be sent
• send a specific value
Value (in %)
(if a value is sent)
0...100
Use malfunction object
No • Yes
Offset in 0,1°C
-10…10; 0
Use external measured value
No • Yes
Ext. Reading proportion of the total reading
5% • 10% • ... • 50% • ... • 100%
All of the following settings are referred to the total value.
Send internal and total reading
• never
• periodically
• on change
• on change and periodically
At and above change of
(if sent on change)
0.1% RH • 0.2% RH • 0.5% RH • 1.0% RH • ...
• 25% RH
Send cycle
(if sent periodically)
5 s • 10 s • ... • 2 h
Use minimum and maximum value
No • Yes
Use threshold value 1/2
Yes • No