Parameter setting
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
5.14. CO2 PI-control
If you activate air quality control, you can use the following settings to define control
type, setpoint values, and ventilation.
General control
The
Sensor KNX AQS/TH-UP Touch
can be used to control one or two-stage venti-
lation.
Configure a block for the ventilation control using the blocking object.
Specify when the current control variables are to be sent to the bus. Periodic sending
is safer, in case a message does not reach a recipient. You may also set up periodic
monitoring using an actuator with this setting.
The status object shows the current status of the output variable (0 = OFF, >0 = ON) and
can for example be used for visualisation.
Controller setpoint
The setpoint values can be set directly in the application program using parameters, or
be defined via the bus using a communication object.
Use control
Yes
• No
Type of control
• One-stage ventilation
• Two-stage ventilation
Behaviour of the blocking object with value
• 1 = block control | 0 = release control
• 0 = block control | 1 = release control
Blocking object value
before first communication
0 • 1
Send control variable
• on change
• on change and periodically
at and above change of (in ppm)
1...20; 2
Cycle
(
if sent periodically)
5 s • ... • 5 min • … • 2 h
Send status object(s)
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(
if sent periodically)
5 s • 10 s • … • 2 h