27
Parameter setting
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
For an adequate regulation of the indoor temperature, comfort, standby, eco and
building protection modes may be used.
Comfort
when present,
Standby
during short absences,
Eco
as a night-time mode and
Frost/heat protection
(building protection) during longer absences.
The settings for the temperature control include the set point temperatures for the
individual modes. Objects are used to determine which mode is to be selected. A
change of mode may be triggered manually or automatically (e.g. by a timer, window
contact).
The
mode
may be switched with two 8 bit objects of different priority. Objects
„... HVAC mode (Prio 2)“ for switching in everyday operation and
„... HVAC mode (Prio 1)“ for central switching with higher priority.
The objects are coded as follows:
0 = Auto
1 = Comfort
2 = Standby
3 = Eco
4 = Building Protection
Alternatively, you can use three objects, with one object switching between eco and
standby mode and the two others activating comfort mode and frost/heat protection
mode respectively. The comfort object blocks the eco/standby object, and the frost/
heat protection object has the highest priority. Objects
„... Mode (1: Eco, 0: Standby)“,
„... comfort activation mode" and
„... frost/heat protection activation mode"
Select the
mode to be activated after reset
(e.g. power failure, reset of the line via
the bus) (Default).
Then configure a temperature control
block
via the blocking object.
Switch mode via
• two 8 Bit objects (HVAC Modes)
• three 1 bit objects
Mode after reset
• Comfort
• Standby
• Eco
• Building protection
Behaviour of the blocking object with value
• 1 = Block | 0 = release
• 0 = block | 1 = release
Blocking object value
before 1st communication
0 • 1