25
Parameter setting
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
a temperature range is given, in which the threshold value can be changed (object val-
ue limit).
A set threshold value will be retained until a new value or a change is transferred. The
current value is saved, so that it is retained in the event of a power supply failure and
will be available once the power supply is restored.
Set the
hysteresis
independent of the type of threshold value specification.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.
Threshold value setting via
Parameter •
Communication objects
The value communicated last shall be
maintained
• never
• after power supply restoration
• after power supply restoration and
programming
Start threshold value in 0.1°C
valid until first communication
-300 … 800; 200
Object value limit (min)
in 0.1°C
-300…800
Object value limit (max)
in 0.1°C
-300…800
Type of threshold value change
Absolute value • Increase/decrease
Increment
(upon increase/decrease change)
0,1 °C • ... • 5°C, 1°C
Hysteresis in % of the threshold value
0 … 50; 20
When the following conditions apply,
the output is
(TV = Threshold value)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1
Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(If delay can be set via objects:
valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(If delay can be set via objects:
valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(only if sending periodically is selected)
5 s • 10 s • 30 s… • 2 h