45
Parameter setting
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
5.11. Comfort field
The
Sensor KNX AQS/TH-UP Touch
can send a message to the bus if the limits of
the comfort field are exceeded. In this way, it is for example possible to monitor com-
pliance with DIN 1946 (standard values) or even to define your own comfort field.
Define the comfort field by specifying the minimum and maximum values for temper-
ature and humidity. The specified standard values comply with DIN 1946
Temperature hysteresis: 1°C
Relative humidity hysteresis: 2% RH
Absolute humidity hysteresis: 2 g/kg
5.12.
CO
2
parameter settings
Select (see
General settings
, Seite 23), whether a
malfunction object
is to be sent if
the sensor is faulty.
Use
Offsets
to adjust the readings to be sent.
The unit can calculate a
mixed value
from its own reading and an external value. Set
the mixed value calculation if desired. If an external portion is used, all of the following
settings (threshold values, etc.) are related to the overall reading.
Use comfort field
No • Yes
Sending pattern
• never
• periodically
• on change
• on change and periodically
Send cycle
(if sent periodically)
5 s • 10 s • 30 s… • 2 h
Maximum temperature in °C
(Standard 26°C)
25 ... 40; 26
Minimum temperature in °C
(Standard 20°C)
10 ... 21; 20
Maximum relative humidity in %
(
Standard 65%)
52 ... 90; 65
Minimum relative humidity in %
(Standard 30%)
10 ... 43; 30
Maximum absolute humidity in 0.1 g/kg
(Standard 115 g/kg)
50 ... 200; 115
Use malfunction object
No • Yes
Offset in ppm
-100…100; 0
Use external measured value
No • Yes
Ext. Reading proportion of the total reading
5% • 10% • ... • 50% • ... • 100%