Parameter setting
Sensor KNX AQS/TH-UP Touch
• Version: 23.10.2018 • Technical changes and errors excepted.
5.
Parameter setting
5.1.
Behaviour on power failure/ restoration of
power
Behaviour following a failure of the bus power supply:
The device sends nothing.
Behaviour on bus restoration of power and following programming or reset:
The device sends all outputs according to their send behaviour set in the parameters
with the delays established in the "General settings" parameter block.
5.2.
General settings
Set the basic data transfer characteristics and select whether or not malfunction ob-
jects should be sent.
5.3.
Temperature value
Use
Offsets
to adjust the readings to be sent.
The unit can calculate a
mixed value
from its own reading and an external value. Set
the mixed value calculation if desired. If an external value is used, all of the following
settings are referred to the total value.
Send delay after power-up and programming for:
Measured values
5 s • ... • 2 h
Threshold values and switching outputs
5 s • ... • 2 h
Controller objects
5 s • 10 s • ... • 2 h
Logic outputs
5 s • 10 s • ... • 2 h
Maximum telegram quota
• 1 message per second
• ...
• 5 messages per second
• ...
• 20 messages per second
Use temp./humidity malfunction object
Yes • No
Use CO2 malfunction object
Yes • No
Offset in 0,1°C
-50…50; 0
Use external reading
Yes • No
Ext. Reading proportion of the total reading
5% • 10% • ... • 50% • ... • 100%
All of the following settings are referred to the total value.