NOVAR 2600 Operating Manual
Measurement & Evaluation
•
three measurement wide range voltage inputs, star / delta / Aron connection
•
three measurement current inputs for xxx/ 5A or xxx /1A CTs connection
•
sampling rate 128/96 samples/period, 10/12 periods evaluation cycle (200 ms at 50/60 Hz)
•
continuous ( gap-less) measurement of voltage and current
•
evaluation of harmonic components up to 40
th
•
fixed window / floating window / thermal average values of all evaluated quantities with
minimum & maximum values registration
•
built-in electricity meter :
•
four-quadrant three tariff electricity meter
•
single phase and three phase energies
•
maximum of average active power value ( power demand )
•
built-in thermometer
Design
•
144x144 mm plastic box for panel mounting
•
LCD graphic display, 5 keys
•
digital input ( 7- & 16-output models only )
•
optional input for external Pt100 temperature sensor
Communication ( Selected Models Only )
•
optional remote communication interface ( RS 485 / Ethernet )
•
optional USB 2.0 communication port for fast data acquisition, configuration and firmware
upgrades
•
proprietary protocol with free data acquisition software ENVIS
•
MODBUS RTU and MODBUS TCP protocols for simple integration with third party SCADA
software
•
embedded webserver ( for instruments with Ethernet interface )
Datalogging Capabilities ( Selected Models Only )
•
battery backed real time circuit (RTC)
•
selection of aggregation intervals from 1 second up to 24 hours
•
high memory capacity for programmable recording of aggregated measurement values
•
automated electricity meter readings at preselected time intervals
7
Summary of Contents for NOVAR 2600
Page 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Page 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Page 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Page 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Page 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...