NOVAR 2600 Operating Manual
Tab 4.4 : Control Parameters
Tab 4.5 : Output Parameters
Default Setup Default Setup
parameter
default setup
target PF 1 / 2
cos; 0.98
control bandwidth 1 / 2
(cos) 0.010
control time – undercomp. 1 / 2
3 minutes
control time – overcomp. 1 / 2
30 seconds
offset power 1 / 2
0 kvars
tariff 2 control
off
tariff 2 control power
0 %
control strategy
3p+1p
choke control
off
choke control limit
(cos) 1.00
offset control
off
42
parameter
default setup
output 1.1÷ 2.9 type /
power / state
zero / 0 kvars /
control
discharge time 1/ 2
30 seconds
output set 2
off
switching mode
intelligent
output recognizer
auto