NOVAR 2600 Operating Manual
Then, in case that :
•
at least one valid output ( capacitor or choke ) was found
•
the instrument is not switched into the
manual
mode
•
no alarm action is active
•
voltage and current higher than measurable minimums at least in one of phases
the instrument starts to control power factor to preset value.
If the undercurrent (
I<
) alarm was disabled for the AOR-process to be able to pass without
any load in the network do not forget to reenable it back !!!
You can found detailed AOR process description in appropriate chapter below.
The instrument includes a row of other parameters – their description is stated in following chapters.
16